Ensuring ducts do not leak may require sealing As a result of the ability to create a slightly pressurized duct system, builders can now use smaller heating and cooling units and smaller duct sizes with assurance of more efficient operations.
The following is taken from HVAC Duct Construction Standards: Metal and Flexible, published by the Sheet Metal and Air Conditioning Contractors’ National Association.
Ducts must be sufficiently airtight to ensure
economical and quiet performance of the system.
It must be recognized that air tightness in ducts
cannot, and need not, be absolute (as it must be in
a water-piping system).
Codes normally require that ducts be reasonably
airtight. Concerns for energy conservation, humidity
control, space-temperature control, room-air
movement, ventilation, maintenance, etc.,
necessitate regulating leakage by prescriptive
measures in construction standards. Leakage is
largely a function of static pressure and the amount
of leakage in a system is significantly related to
system size. Adequate air tightness can normally be
ensured by:
A. Selecting a static pressure construction class
suitable for the operating condition.
B. Sealing the ductwork properly.
The designer is responsible for determining the
pressure class or classes required for duct
construction and for evaluating the amount of
sealing necessary to achieve system-performance
objectives. It is recommended that all duct
constructed for the 1-inch (250 Pascal) and
half-inch (125 Pascal) pressure class meet Seal
Class C.
However, because designers sometimes deem leakage in
unsealed ducts not to have adverse effects, the
sealing of all ducts in the 1-inch and half-inch
pressure class is not required by this construction
manual. Designers occasionally exempt the following
from sealing requirements: small systems,
residential occupancies, ducts located directly in
the zones they serve, ducts that have shot runs from
volume-control boxes to diffusers, certain
return-air ceiling plenum applications, etc.
When Seal Class C is to apply to all 1-inch and
half-inch pressure-class duct, the designer must
require this in the project specification. The
designer should review the HVAC Air Duct Leakage
Test Manual for estimated and practical leakage
allowances.
Seven pressure classes exist: half-inch, 1 inch, 2
inch (500 Pascal), 3 inch (750 Pascal), 4 inch
(1,000 Pascal), 6 inch (1,500 Pascal) and 10 inch
(2,500 Pascal) water gauge. If the designer does not
designate pressure class for duct construction on
the contract drawings, the basis of compliance with
the SMACNA HVAC duct-construction standards is as
follows: 2-inch w.g. for all ducts between supply
fan and variable-volume control boxes and 1-inch w.g.
for all other ducts of any application.
Leakage tests
If testing is performed, points are awarded to
the builder and contractor for better than expected
results (third party).
Read more
There is no need to verify leakage control by
field-testing when adequate methods of assembly and
sealing are used. Leakage tests are an added expense
in system installation. It is not recommended that
duct systems constructed to 3-inch w.g. class or
lower be tested because this is generally not
cost-effective.
For duct systems constructed to 4-inch w.g. class
and higher, the designer must determine if any
justification for testing exists. If it does, the
contract documents must clearly designate the
portions of the system(s) to be tested and the
appropriate test methods. ASHRAE (American Society
of Heating, Refrigerating and Air-Conditioning
Engineers) energy conservation standards Series 90
text on leakage control generally requires tests
only for pressures in excess of 3 inch.
The HVAC Air Duct Leakage Test Manual provides
practical and detailed procedures for conducting
leakage tests.
Apparent differences of about 10 percent between fan
delivery and sum of airflow measurements at
terminals do not necessarily mean poor sealing and
excess leakage. Potential accuracy of flow
measurements should be evaluated.
Otherwise, open access doors, unmade connections,
missing end caps or other oversights contribute to
such discrepancies. When air terminals are at a
great distance from fans (over 500 feet), more
effective sealing is probably required to avoid
diminished system performance.
Schools, shopping centers, airports and other
buildings may use exposed ductwork. Selecting
sealing systems for such ducts may involve more
attention to the final appearance of the duct system
than with ducts in concealed spaces.
Conclusion:
Long-standing industry acceptance of so-called
low-pressure duct systems without sealants may have
left some contractors (and designers) with little or
no experience with sealing. The contractor should
follow carefully select construction details
submitted on this WEB site for sealing requirements,
the direction of the air pressure and familiar
sealing methods. The cost of restoring systems not
receiving the required sealing can greatly exceed the
modest cost of a proper application.
Content prepared for CDC ENTERPRISES, INC by Luciano Management, Published in agreement with sources; Energy Star, DOE, SMACNA, ASREA, ICC, UMC, ACCA Manual D & Manual J