AIR LEAKAGE

Because HDPE QADUCT air ducts are new to the HVAC  industry today engineers are applying current standards as a gap measurement.

 

We recommend the ASHRAE U.S. Code Acceptance as a method to interpret Air Flow pressure
SPC 118.2-1993R - Revision project committee authorized 98/01/17, with same TPS ANSI/ASHRAE 119-1988 (RA 1994) - (Reaffirmation of ANSI/ASHRAE Standard 119-1988) Air Leakage Performance for Detached Single-Family Residential Buildings PURPOSE:

1.1 This standard establishes performance requirements for air leakage of residential buildings to reduce the air infiltration load. See DOE IECC changes or DOE Site

1.2 This standard provides a method to classify the air tightness of residential buildings.

2 SCOPE

2.1 This standard sets upper limits of leakage area and provides a method of classifying air tightness for detached, single-family residential buildings.

2.2 This standard does not apply to buildings which are conditioned for human comfort less than 876 hours of the year.

2.3 Although this standard is intended to reduce energy use associated with air leakage through the envelope of residential buildings, use of this standard may preclude the use of air infiltration alone to achieve adequate indoor air quality. The reduction of air leakage is separate from the need to provide adequate ventilation, adequate combustion air and adequate indoor air quality. Consideration of these issues is the responsibility of the user.

 

Measuring Characteristics IAQ
QADUCT™ is an engineered high-density polyethylene plastic ductwork system which together with clamp and gasket is air-tight, more energy efficient air-transfer system than traditional metal ducts.  But energy efficiency is not the only benefit, the goal is to improve air quality by also reducing air infiltration and RADON.
 

Two goals to keep in mind, tightening the house and maintaining indoor air pressure at 2 Pascals (0.008” water column) relative to soil gas pressure. Radon level at 1.7 pCi/L, can be reduction by 93%. This is similar to results achieved by EPA scientists who reported reducing indoor radon levels by more than 90% in test homes by keeping indoor air pressure up to 4 Pascals (0.015” water column) greater than the surrounding soil gas pressure. (also see “Radon Reduction Techniques for Detached Houses”, Page 154, EPA/625/5-87/019).

 

 

This calculation serves to indicate the Duct Pressure class required. In this case, it will be seen that Class 3 SMACNA leakage rate is 0.15 L/s per m2 against 0.121 L/s per m2 required.




 

 Manometers measure a pressure difference by balancing the weight of a fluid column between the two pressures of interest. Large pressure differences are measured with heavy fluids, such as mercury (e.g. 760 mm Hg = 1 atmosphere). Small pressure differences, such as those experienced in experimental wind tunnels or venturi flow meters, are measured by lighter fluids such as water (27.7 inch H2O = 1 psi; 1 cm H2O = 98.1 Pa).




 

 

Duct System performance shall not exceed SMACNA’s Leakage Class 3 requirements at the system design static pressure as indicated on the exceed -20 in  or +12 in W.G. Read More

 

References
QADUCT  components are constructed per SMACNA’s Duct Construction Standards for to operate on air leakage design tightness at 0.1 inch minimum water column pressure. For better comfort, the performance system can reach 10 inches water column pressure @ 5000 cfm with better sealing.  We recommend MAXSEAL with AKDUCT clamps. For further technical information please contact us support@cdcei.net

High Velocity systems are measured at  600 CFM at 1.5” in W.G. Standard Pressure.

 

 

Conclusion:

Soil gas pressure under a typical building is higher than outdoor air pressure, so keeping indoor air pressure higher than soil gas pressure will also keep indoor air pressure higher than outdoor air pressure.

 

Content prepared by Luciano Management, Published in agreement with sources; Energy Star, DOE, SMACNA, ASREA, ICC, UMC, ACCA Manual D & Manual J